Google’s AI Data Centers Become Grid Partners
Google 正通过全栈设计把 AI 数据中心变成电网的主动合作伙伴:其 AI 算力需求从 2025 年 5 月到 2026 年 5 月增长七倍,月处理超 3 千万亿 token。Google 用 BESS 储能、54 VDC 机架级电池备份和液冷替代传统集中式 UPS,并计划逐步迁移到 800 VDC 配电。Google 还与 Meta、Microsoft、Nvidia 共同制定公用事业与超大规模厂商的接口规范。
正文
当前显示原文,中文全文译文尚未就绪。
At Data Center World Power, Google’s Tom Garvens detailed how full-stack design, LVDC power, BESS, and liquid cooling are reshaping hyperscale AI while supporting local grids.
September 25, 2026
AI infrastructure is expanding at an unprecedented pace. Google now processes more than 3 quadrillion AI tokens per month, representing a sevenfold increase in compute demand from May 2025 to May 2026. Meeting this velocity requires innovation in energy efficiency and power delivery.
Tom Garvens, vice president of advanced technology innovation at Google, outlined this challenge during a keynote at Data Center World Power 2026 in Houston, held Sept. 21-23. He described Google’s full-stack approach to scaling AI, positioning data centers as active partners in stabilizing local grids.
To bridge the speed mismatch between rapid AI rollout and multiyear timelines typical for utility capacity expansion, Google has developed energy strategies that transform backup assets into grid-supportive resources, streamline operations during peak demand, make load shaping more intelligent, and prevent disruptive power swings – while supporting utility resilience.
Beyond these strategies, Google is reviewing and redesigning the entire AI data center ecosystem – from chip to utility. This includes optimizing for liquid cooling, low-voltage direct current (LVDC) architectures, intelligent algorithms, and facility design. A core pillar of this work is publishing standardized power and facility technology specifications through communities such as the Open Compute Project (OCP), enabling the industry to build interoperable, efficient, and sustainable infrastructure.
“Google has tightly coupled vertical integration in AI along with close partnerships with energy providers,” Garvens said. “We develop and design our own data centers, chips, servers, and rack designs. By having control of our entire hardware and software stack, we can optimize these things together for sustainability and energy efficiency.”
Powering AI at Gigawatt Scale
Google is investing alongside utilities to add grid capacity. That assistance is vital as a gigawatt-class data center campus can comprise hundreds of thousands of interconnected chips running a single workload. Google’s approach is twofold: work with utility partners to streamline power delivery and adjust its own hardware and software to be more grid-friendly.
“Utilities are [setting] different requirements that we must demonstrate that we can meet,” Garvens noted. “Google, Meta, Microsoft, and Nvidia have come together to define an interface spec on how utilities and hyperscalers can interface with each other.”
Battery energy storage systems (BESS) have become critical in Google’s campus designs for onsite energy storage and for buffering rapidly fluctuating workloads. Buffering smooths power and voltage transitions. Backup generators remain in use, but diesel does not scale well to campuses at 1 GW and beyond. BESS are increasingly used to provide standby power, supported by demand-response agreements with utilities for peak shaving.
“When peak needs are beyond what we've got power for, we can get that from local storage,” Garvens explained.
Rather than competing for constrained capacity in saturated markets, Google has been identifying remote sites with ample land and available power. The company is also considering campus developments in small towns where the data center would be a primary employer, he said.
Another design change: Google has moved away from centralized Uninterruptible Power Supply (UPS) systems, favoring rack-level battery backup operating around 54 VDC. Eliminating an extra AC-DC-AC conversion step yields approximately a 1.5% efficiency gain.
“We do all of our power conversion at the top of our racks, where we take our AC down to 54 volts, and then we run DC through our racks; our battery backup also runs at that voltage,” Garvens said.
Google has introduced changes at the chip, rack, and facility levels, supported by software that can intermix workloads to smooth overall load and make it more predictable.
Rack density remains a major challenge. Roadmaps anticipate racks approaching 1 MW each over the next year or two. That necessitates liquid cooling for at least the hotter elements within the racks.
Delivering the required current at lower voltages would demand bus bars and cabling with significantly more copper. This calls for a higher distribution voltage. Google is pursuing a gradual migration toward 800 VDC for power distribution, which is expected to take a couple of years to mature.
In the meantime, Google has implemented “sidecars” alongside its racks – adjacent power-distribution enclosures that house cabling and power gear – reserving the racks for high-density servers. The tradeoff is floor space. When 800 VDC becomes broadly available, those sidecars can be converted to additional AI server racks.
“We're working with the industry on bringing solid-state transformers to maturity,” Garvens said. “We are also continuing to improve our power usage effectiveness [PUE]. We can't ever get to 1.0, but we continue to challenge ourselves to get as close to it as possible.”
With dozens of data centers in operation and many more in development, Google can be fluid about where it runs workloads. Garvens offered an example:
“If there's a heat wave in Ohio and we were running a big workload, we've got agreements in place whereby with the right amount of foresight we can shut certain workloads down or move them elsewhere if they're critical,” he said. “We have a portfolio where we can shift things around.”
Water strategy is another focus area. The company is investing in closed-loop cooling systems – sealed liquid circuits where the working fluid remains within the system and makeup water is minimized. This marks a shift from designs that consumed large quantities of water. There is no single approach; depending on conditions – altitude, humidity, water table, drought risk, and community needs – Google works with partners to determine the appropriate power capacity and the best cooling design.
“We work with our partners in terms of what's available and figure out what is the right amount of power we can get and what water usage or closed-loop design is most appropriate,” Garvens noted.
Keeping Pace with Silicon Roadmaps
Each new generation of silicon tends to draw more power, and multiple chips are arriving every year.
“The most precious thing we have is a watt: you don't want to ever strand a watt,” Garvens said. “So, making our data center and our designs as crisp as we can for as far out as we can see in these roadmaps, it's why our partnerships with our silicon and GPU design teams are so critical.”
Drew Robb has been a full-time professional writer and editor for more than twenty years. He currently works freelance for a number of IT publications.
Want more Data Center Knowledge stories in your Google search results?
Editor's Choice
Aug 21, 2026
Want more Data Center Knowledge stories in your Google search results?
Join the entire data center ecosystem September 21 – 23, 2026, at the Gaylord Texan Resort & Convention Center in Dallas, TX.